Section 3: Installation

Reference, Installation, and Operations Manual

June 2013

3-9000-743 Rev S

 

 

3.5.5Series 100 Plus Option Board Analog Input switch settings

The Series 100 Plus Option Board provides the capability to sample analog temperature (Analog Input 1) and pressure (Analog Input 2) 4-20 mA signals. These input signals are individually configurable for sinking or sourcing current via Series 100 Plus Option Board switches as described in the tables below (Table 3-39through Table 3-46) and in Daniel drawing DE-21056 (particularly page 3, notes 24, 25, and 28 (see Appendix I). The Series 100 Plus Option Board provides two independent analog input circuits used in conventional 4-20 mA service.

If the analog input is configured for ‘Source’ mode (i.e., powered by the meter), then it must be at the bottom of the loop (stack).

Table 3-39 Series 100 Plus Option board Analog In 1 temperature sink setting

Board

Switch

Position

 

 

 

Series 100 Plus Option Board

S12-1

SINK

 

 

 

 

S12-2

SINK

 

 

 

 

S12-3

SINK

 

 

 

84

Series 100 Plus Option Board Analog Input switch settings