Section 3: Installation

3.1Installation instructions

HAZARDOUS VOLTAGE INSIDEDo not open enclosure in flammable gas area.

Failure to follow the instructions in this manual may result in serious injury or death.

EXPLOSION HAZARD

Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous.

Substitution of components may impair intrinsic safety.EXPLOSION OR FIRE HAZARD

Conduit runs must have a sealing fitting within 50mm (2 inches) of the enclosure to reduce the risk of an explosion or a fire.

During operation, keep covers tight.

During equipment maintenance, disconnect power before opening transmitter or base electronics. Clean cover joints before replacing.

DO NOT substitute meter components. Component substituting may compromise the intrinsic safety.

Failure to do so may result in severe injury to personnel or cause damage to the equipment.