5.6.8Current Outputs Page

Figure 5-11 Field Setup Wizard - Meter Current Outputs Page1.From the Current Outputs Page, choose the desired settings:Content:Current output 1 Current output 2

Options: Actual flow rate (Uncorrected), Standard flow rate (Corrected), Average flow velocity, Average sound velocity, Energy rate, or Mass rate (Energy rate or Mass rate available if selected on Frequency outputs page)

Direction:ReverseForwardAbsolute

Full scale volumetric flow rate used with output:

Options: US Customary - ft3/sec.,hr, day or Metric - m3/sec.,hr, dayAlarm Action:High - 20 mALow - 4 mAHold Last ValueVery Low - 3.5 mAVery High - 20.5 mANone

140