Section 3: Installation

Reference, Installation, and Operations Manual

June 2013

3-9000-743 Rev S

 

 

Table 3-42 Series 100 Plus Option board Analog In 2 pressure source setting

Board

Switch

Position

 

 

 

Series 100 Plus Option Board

S13-1

SRC

 

 

 

 

S13-2

SRC

 

 

 

 

S13-3

SRC

 

 

 

3.5.6Series 100 Plus Option Board Analog Output switch settings

The Series 100 Plus Option Board provides two 4-20 mA analog output signals that are hardware configurable to either sink or source current as described in Table 3-43and Table 3-44below and in Daniel drawing DE-21056 (see Appendix I).

If the analog output is configured for ‘source’ mode (i.e., powered by the meter), then it must be at the bottom of the loop (stack). The HART® output cannot be multi-dropped when configured for source mode.

Full HART® functionality is provided so that any commercially available HART® transmitter which meets the specifications of the HART® Communications Foundation can be connected to the Daniel® Ultrasonic Gas Flow Meter.

Table 3-43 Series 100 Plus Option Board Analog Out 1 sink settings

Board

Switch

Position

 

 

 

Series 100 Plus Option Board

S14-1

SINK

 

 

 

 

S14-2

SINK

 

 

 

 

S14-3

SINK

 

 

 

86

Series 100 Plus Option Board Analog Output switch settings