Reference, Installation, and Operations Manual

Section 5: Startup and meter configuration

3-9000-743 Rev S

June 2013

 

 

 

1.From the HART Output Page, choose the desired settings (Refer to Daniel P/N 3-9000- 754 HART® Field Device Specification Guide: Daniel Gas Ultrasonic Meter manual for a detailed discussion on configuring the HART® outputs.) The manual is available on the Daniel website:

http://www2.emersonprocess.com/en-US/brands/daniel/Flow/ultrasonics/Pages/Ultrasonic.aspx

Process variables are the four dynamic HART variables which you can configure for the Daniel Ultrasonic Gas meter. The Primary variable is set to match the Content set for Current Output 2. If you want a different Primary variable, you will need to go back to the Current Output Page and choose a different selection for its Content control for Current Output 2.

a.Process Variable:Primary variable2nd variable3rd variable4th variable

b.Options: Uncorrected (Actual) flow rate, Corrected flow rate, Average flow velocity, or Average sound velocity, Energy rate, Mass rate, Pressure rate, or Temperature rate

Identification: Tag -Date -Message -Descriptor -Final assembly number -Polling address -c.HART® units:Volume units -Flow rate time units -Velocity units -Pressure units -Temperature units -

2.Click the Next button to continue the meter configuration. Daniel MeterLink displays the Field Setup Wizard - Meter Digital Outputs Page.

HART® Output Page