Section 5: Startup and meter configuration

Reference, Installation, and Operations Manual

June 2013

3-9000-743 Rev S

 

 

Table 5-4 Data Points for serial ports configuration
Daniel MeterLink Display Name

Data Points, Options and Guidelines

 

 

Comms Address

Data points affected:

 

ModbusIDPortA

 

ModbusIDPortB

 

ModbusIDPortC

 

Options:

 

Enter a value (integer) within the range [1,247]

 

 

Baud rate

Data points affected:

 

BaudPortA

 

BaudPortB

 

BaudPortC

 

Options:

 

1200

 

2400

 

9600

 

19200

 

38400

 

57600

 

115200

 

 

Response delay

Data points affected:

 

CommRspDlyPortA

 

CommRspDlyPortB

 

CommRspDlyPortC

 

Options:

 

Enter an integer value (milliseconds) within the range [0,100]

 

 

RTS on delay

Data points affected:

 

RTSOnDelayPortA

 

Options:

 

Enter an integer value (milliseconds) within the range [0,1000]

 

 

RTS off delay

Data points affected:

 

RTSOffDelayPortA

 

Options:

 

Enter an integer value (milliseconds) within the range [0,1000]

 

 

RTS/CTS flow ctrl

Data points affected:

 

IsHWFlowControlEnabledPortA

 

Options:

 

Disable (FALSE)

 

Enable (TRUE)

 

 

 

110

Serial port connections using RS-232 serial cable