AGA 8 Setup page

Section 5: Startup and meter configuration

Reference, Installation, and Operations Manual

June 2013

3-9000-743 Rev S

 

 

1.From the Field Setup Wizard - AGA 8 Page, choose the desired settings:AGA8 calculations to be performed:Internally (by meter)Base temperatureBase pressureBase absolute pressureExternallyFixedLiveTable 5-20 Field Setup Wizard - AGA 8 Setup
AGA8 methodConfiguration Parameters

 

 

Gross Method 1

Specific gravity: Relative density; used as input to the AGA8 Gross Methods 1 and 2 calculations

 

Reference temperature - for the specific gravity

 

Reference pressure - for specific gravity

 

CO2 - Mole percentage CO2 in the natural gas mixture

 

Hydrogen - Mole percentage of hydrogen

 

CO - Mole percentage of carbon monoxide

 

Volumetric gross heating

 

Molar density ref temperature: Reference temperature for the molar density; used as

 

input to the AGA8 Gross Method 1 calculation

 

Molar density ref pressure: Reference pressure for the molar density; used as input to the

 

AGA8 Gross Method 1 calculation

 

 

Gross Method 2

Specific gravity: Relative density; used as input to the AGA8 Gross Methods 1 and 2 calculations

 

Reference temperature - for the specific gravity

 

Reference pressure - for the specific gravity

 

CO2 - Mole percentage CO2 in the natural gas mixture

 

Hydrogen - Mole percentage of hydrogen

 

CO - Mole percentage of carbon monoxide

 

Nitrogen - Mole percentage of nitrogen in the natural gas mixture (AGA8 Gross Method 2

 

calculation)

 

 

AGA8 method

Configuration Parameters

 

 

Detail

Enter the amount of each of the 21 gas components as a percentage.

 

This option is only available in Mark III meters

 

Gas composition - Select either the Fixed or Live GC.

 

Fixed: Select this option to use the fixed gas composition stored in the meter for all

 

 

calculations for which they are required.

 

Live GC: Select this option to use a gas composition collected by the meter from a

 

 

gas chromatograph for all calculations for which they are required. This option is

 

 

only available for Mark III meters with a valid GCKey

 

 

Externally

Select if AGA8 calculations are done externally. The calculated values must then be

 

written to the meter using Daniel MeterLink or a flow computer. The following properties

 

must be entered. If a flow computer or SCADA system is used to write these values to the

 

meter, they do not have to be entered at this time.

 

Flow mass density

 

Flow compressibility

 

Base compressibility

 

 

 

Note: Mark II meters - Externally calculating the AGA8 calculations is only available for DFI boards running version 3.40 or later

firmware.

156