For personal safety, connect the green and yellow wire to safety (earth) ground at both the switch and the supply side of the DC wiring.

The marked input voltage of –48 VDC for a DC-powered switch is the nominal voltage associated with the battery circuit, and any higher voltages are only to be associated with float voltages for the charging function.

Because the switch is a positive ground system, you must connect the positive lead to the terminal labeled RTN, the negative lead to the terminal labeled

–48 VDC, and the earth ground to the chassis grounding points.

Related Topics General Safety Guidelines and Warnings for EX Series Switches on page 207

General Electrical Safety Guidelines and Warnings for EX Series Switches on page 235

DC Power Disconnection Warning for EX Series Switches on page 242

DC Power Grounding Requirements and Warning for EX Series Switches on page 244

DC Power Wiring Sequence Warning for EX Series Switches on page 245

DC Power Wiring Terminations Warning for EX Series Switches on page 246

Connecting DC Power to an EX3200 or EX4200 Switch on page 148

Connecting DC Power to an EX8200 Switch

DC Power Disconnection Warning for EX Series Switches

WARNING: Before performing any of the DC power procedures, ensure that power is removed from the DC circuit. To ensure that all power is off, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position.

Waarschuwing Voordat u een van de onderstaande procedures uitvoert, dient u te controleren of de stroom naar het gelijkstroom circuit uitgeschakeld is. Om u ervan te verzekeren dat alle stroom UIT is geschakeld, kiest u op het schakelbord de stroomverbreker die het gelijkstroom circuit bedient, draait de stroomverbreker naar de UIT positie en plakt de schakelaarhendel van de stroomverbreker met plakband in de UIT positie vast.

Varoitus Varmista, että tasavirtapiirissä ei ole virtaa ennen seuraavien toimenpiteiden suorittamista. Varmistaaksesi, että virta on KATKAISTU täysin, paikanna tasavirrasta huolehtivassa kojetaulussa sijaitseva suojakytkin, käännä suojakytkin KATKAISTU-asentoon ja teippaa suojakytkimen varsi niin, että se pysyy KATKAISTU-asennossa.

Attention Avant de pratiquer l'une quelconque des procédures ci-dessous, vérifier que le circuit en courant continu n'est plus sous tension. Pour en être sûr, localiser le disjoncteur situé sur le panneau de service du circuit en courant continu, placer

242DC Power Disconnection Warning for EX Series Switches