Settings

 

 

 

 

Chapter 4 Parameters

Settings

Function

Description

 

 

 

Operation

 

ON: Operation command via Communication

 

 

 

Command

 

 

 

 

 

OFF: Operation command via Pr.02.01 setting

 

 

20

Selection (Pr 02.01

 

 

 

setting/

 

Pr.02.01 is disabled if this parameter value 20 is set. See the

 

 

explanation below this table.

 

 

 

Communication)

 

 

 

 

 

 

 

 

 

 

 

 

 

21

Forward/Reverse

This function has top priority to set the direction for running (If

“Pr.02.04=0”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Source of second

Used to select the first/second frequency command source. Refer

 

to Pr.02.00 and 02.09.

 

 

22

frequency

 

 

 

 

ON: 2nd Frequency command source

 

 

 

command enabled

 

 

 

OFF: 1st Frequency command source

 

 

 

 

 

 

 

 

 

 

 

04.09

Multi-function Input Contact Selection

Unit: 1

 

 

 

 

 

 

Settings

0 to 4095

Factory Setting: 0

 

 

 

 

 

 

 

This parameter can be used to set the status of multi-function terminals (MI1~MI6 (N.O./N.C.) for standard AC motor drive).

The MI1~MI3 setting will be invalid when the operation command source is external terminal

(2/3wire).

 

 

 

 

 

 

 

Weights

 

 

 

 

 

 

0=N.O

Bit

5

4

3

2

1

0

1=N.C

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

The Setting method: It needs to convert binary number (6-bit) to decimal number for input.

For example: if setting MI3, MI5, MI6 to be N.C. and MI1, MI2, MI4 to be N.O. The setting value Pr.04.09 should be bit5X25+bit4X24+bit2X22= 1X25+1X24+1X22= 32+16+4=52 as shown in the following.

Revision August 2008, 2ELE, V1.02

4-61