| Chapter 4 Parameters | ||
Settings | Function | Description |
|
| ||
| Operation |
| ON: Operation command via Communication |
|
| |
| Command |
|
|
| ||
|
| OFF: Operation command via Pr.02.01 setting |
|
| ||
20 | Selection (Pr 02.01 |
|
| |||
| setting/ |
| Pr.02.01 is disabled if this parameter value 20 is set. See the | |||
|
| explanation below this table. |
|
| ||
| Communication) |
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
21 | Forward/Reverse | This function has top priority to set the direction for running (If | ||||
“Pr.02.04=0”) |
|
| ||||
|
|
|
|
| ||
|
|
|
|
|
| |
| Source of second | Used to select the first/second frequency command source. Refer | ||||
| to Pr.02.00 and 02.09. |
|
| |||
22 | frequency |
|
|
| ||
| ON: 2nd Frequency command source |
|
| |||
| command enabled |
|
| |||
| OFF: 1st Frequency command source |
|
| |||
|
|
|
|
| ||
|
|
|
| |||
04.09 | Unit: 1 | |||||
|
|
|
|
| ||
| Settings | 0 to 4095 | Factory Setting: 0 | |||
|
|
|
|
|
|
|
This parameter can be used to set the status of
The MI1~MI3 setting will be invalid when the operation command source is external terminal
(2/3wire). |
|
|
|
|
|
|
|
Weights |
|
|
|
|
|
| 0=N.O |
Bit | 5 | 4 | 3 | 2 | 1 | 0 | 1=N.C |
MI1 | |||||||
|
|
|
|
|
|
| MI2 |
|
|
|
|
|
|
| MI3 |
|
|
|
|
|
|
| MI4 |
|
|
|
|
|
|
| MI5 |
|
|
|
|
|
|
| MI6 |
The Setting method: It needs to convert binary number
For example: if setting MI3, MI5, MI6 to be N.C. and MI1, MI2, MI4 to be N.O. The setting value Pr.04.09 should be bit5X25+bit4X24+bit2X22= 1X25+1X24+1X22= 32+16+4=52 as shown in the following.
Revision August 2008, 2ELE, V1.02 |