Chapter 4 Parameters

Settings

Function

Description

14

Heat Sink Overheat

When heatsink overheats, it will signal to prevent OH turn off

Warning

the drive. When it is higher than 85oC (185oF), it will be ON.

 

 

 

 

15

Over Voltage supervision

Active when the DC-BUS voltage exceeds level

 

 

 

16

PID supervision

Active when the PID feedback signal is abnormal (Refer to

Pr.10.12 and Pr.13.)

 

 

17

Forward command

Active when the direction command is FWD

 

 

 

18

Reverse command

Active when the direction command is REV

 

 

 

19

Zero Speed Output

Active when the drive is standby or stop

Signal

 

 

 

 

 

 

Communication Warning

 

20

(FbE,Cexx, AoL2, AUE,

Active when there is a Communication Warning

 

SAvE)

 

 

 

 

21

Brake Control (Desired

Active when output frequency Pr.03.11. Deactivated when

Frequency Attained)

output frequency Pr.03.12 after STOP command.

 

 

 

 

22

AC Motor Drive Ready

Active when AC motor drive is ready.

 

 

 

03.01Reserved

03.02

Desired Frequency Attained

Unit: 0.01

 

Settings

0.00 to 600.0 Hz

Factory Setting: 0.00

 

 

 

 

If a multi-function output terminal is set to function as Desired Frequency Attained (Pr.03.00 =09), then the output will be activated when the programmed frequency is attained.

4-48

Revision August 2008, 2ELE, V1.02

Page 91
Image 91
Delta Electronics VFD-EL manual 03.02