Chapter 4 Parameters

MI1-DCM (close)

 

 

 

 

ON

OFF ON

 

 

OFF

 

 

 

 

power is applied

ON

 

 

 

 

 

 

 

 

output frequency

Pr.02.05=0 or 1 it will run

output frequency Pr.02.05=2 or 3

it won't run

when power is applied It needs to received a run command after previous command is cancelled

The Line Start Lockout feature does not guarantee that the motor will never start under this condition. It is possible the motor may be set in motion by a malfunctioning switch.

02.06Loss of ACI Signal (4-20mA)

 

 

Factory Setting: 0

Settings

0

Decelerate to 0Hz

 

1

Coast to stop and display “AErr”

 

2

Continue operation by the last frequency command

 

 

 

This parameter determines the behavior when ACI is lost.

When set to 1, it will display warning message “AErr” on the keypad in case of loss of ACI signal and execute the setting. When ACI signal is recovered, the warning message will stop blinking. Please press “RESET” key to clear it.

02.07

Up/Down Mode

 

 

 

 

 

Factory Setting: 0

 

 

Settings

0

By digital keypad up/down keys mode

 

 

 

 

1

Based on Accel/Decel Time acc. to Pr.01.09 to 01.12

 

 

 

2

Constant speed (acc. to Pr. 02.08)

 

 

 

 

3

Pulse input unit (acc. to Pr. 02.08)

 

 

 

 

 

 

02.08

Accel/Decel Rate of Change of UP/DOWN Operation with

Unit: 0.01

 

Constant Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings

0.01~10.00 Hz/2ms

Factory Setting: 0.01

 

 

 

 

 

 

Revision August 2008, 2ELE, V1.02

4-43

Page 86
Image 86
Delta Electronics VFD-EL manual 02.07, 02.08