Chapter 4 Parameters
| Settings | Function | |
10 | UP: Increase | ||
Master Frequency | |||
|
| ||
|
|
| |
11 | DOWN: Decrease | ||
Master Frequency | |||
|
|
12Counter Trigger
13Counter Reset
14External Fault
15 | PID function | |
disabled | ||
| ||
|
| |
16 | Output Shutoff Stop | |
|
| |
17 | Parameter lock | |
enable | ||
|
Operation
Command
18Selection (Pr.02.01 setting/external terminals)
Operation Command
19Selection (Pr 02.01 setting/Digital Keypad)
Description
Increase/decrease the Master Frequency each time an input is received or continuously when the input stays active. When both inputs are active at the same time, the Master Frequency increase/decrease is halted. Please refer to Pr.02.07, 02.08. This function is also called “motor potentiometer”.
Parameter value 12 programs one of the
When active, the counter is reset and inhibited. To enable counting the input should be OFF. Refer to Pr.03.05 and 03.06.
Parameter value 14 programs one of the
When an input ON with this setting is ON, the PID function will be disabled.
AC motor drive will stop output and the motor free run if one of these settings is enabled. If the status of terminal is changed, AC motor drive will restart from 0Hz.
When this setting is enabled, all parameters will be locked and write parameters is disabled.
ON: Operation command via Ext. Terminals
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 18 is set. See the explanation below this table.
ON: Operation command via Digital Keypad
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 19 is set. See the explanation below this table.
Revision August 2008, 2ELE, V1.02 |