| Chapter 4 Parameters |
Group 6: Protection Parameters |
|
| |
|
|
| |
06.00 | Unit: 0.1 | ||
| Settings 115V/230V series | 330.0 to 410.0V | Factory Setting: 390.0 |
| 460V series | 660.0 to 820.0V | Factory Setting: 780.0 |
0Disable
During deceleration, the DC bus voltage may exceed its Maximum Allowable Value due to motor regeneration. When this function is enabled, the AC motor drive will not decelerate further and keep the output frequency constant until the voltage drops below the preset value again.
![]()
![]()
![]()
NOTE
With moderate inertia load,
high voltage at DC side
time
output
frequency ![]()
Frequency Held
Deceleration characteristic when
time
previous deceleration time
actual time to decelerate to stop when