Delta Electronics VFD-EL manual Ground Fault, Over Voltage OV, Troubleshooting

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 153
Image 153
Chapter 5 Troubleshooting

Chapter 5 Troubleshooting5.2 Ground Fault

5.2 Ground Fault

GFF

Ground fault

5.3 Over Voltage (OV)

Is output circuit(cable or

 

No

motor) of AC motor drive

 

 

 

grounded?

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

Remove ground fault

 

 

 

 

 

 

 

Maybe AC motor drive has malfunction or misoperation due to noise. Please contact DELTA.

Over voltage

Reduce voltage to

No Is voltage within

be within spec.

 

specification

 

 

 

Yes

 

 

 

 

 

 

 

Maybe AC motor drive has malfunction or misoperation due to noise. Please contact 5.3 Over Voltage (OV) with DELTA.

Has over-voltage occurred without load Yes No

No When OV occurs, check if the voltage of DC BUS is greater than protection value

YesYes

No

Reduce moment of inertia

Dose OV occur when

Increase

Yes

sudden acceleration

deceleration

 

 

 

 

 

 

stops

 

 

time

 

 

 

 

 

 

Yes

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Increase

Yes

 

 

 

 

 

 

 

acceleration

 

 

 

Increase setting time

 

 

 

 

 

 

 

time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

Need to consider using

No

 

 

 

 

 

 

 

 

 

 

 

 

Reduce moment of load inertia

braking unit or

 

 

DC braking

 

No

 

 

 

No

Use braking unit or DC braking

 

 

Yes

 

 

 

 

Need to check control method. Please contact DELTA.

5-2

Revision August 2008, 2ELE, V1.02

Page 153
Image 153
Delta Electronics VFD-EL manual Ground Fault, Over Voltage OV, Troubleshooting