Chapter 4 Parameters

Weights

 

 

 

 

 

 

0=N.O

 

 

 

 

 

 

1=N.C

Bit

1

1

0

1

0

0

MI1

MI2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MI6

 

 

 

 

 

 

 

 

 

 

 

 

 

The setting value

 

NOTE:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

= bit5x2

5

+bit4x2

4

+bit2x2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

14

=16384

2

13

=8192

2

12

=4096

2

11

=2048

2

10

 

= 1x2

5

+1x2

4

+1x2

2

 

 

 

 

 

 

 

=1024

 

 

 

 

 

2

9

=512

2

8

=256

2

7

=128

 

6

 

 

2

5

=32

 

=32+16+4 =52

 

 

 

 

 

 

 

2 =64

 

 

 

 

 

 

4

 

 

 

3

 

 

 

2

 

 

 

 

1

 

 

0

 

 

 

Setting 04.09

 

 

 

2

 

=16

2

 

=8

2 =4

2 =2

 

2 =1

04.10

Digital Terminal Input Debouncing Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: 2 msec

 

Settings

 

 

 

 

 

1 to 20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 1

 

This parameter is to delay the signals on digital input terminals. 1 unit is 2 msec, 2 units are 4

 

msec, etc. The delay time is to debounce noisy signals that could cause the digital terminals to

 

malfunction.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04.26 Display the Status of Multi-function Input Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings

 

 

 

 

 

Read Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory setting: ##

 

Display

 

 

 

 

 

Bit0: MI1 Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit1: MI2 Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit2: MI3 Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit3: MI4 Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit4: MI5 Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit5: MI6 Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The multi-function input terminals are falling-edge triggered. For standard AC motor drive,

 

there are MI1 to MI6 and Pr.04.26 will display 63 (111111) for no action.

 

 

 

Weights

 

 

 

 

 

 

0=Active

Bit

5

4

3

2

1

0

1=off

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

4-62

Revision August 2008, 2ELE, V1.02

Page 105