Delta Electronics VFD-EL manual RS-485, Group 9 Communication Parameters, 09.00

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 127
Image 127
RS-485

Chapter 4 Parameters09.00

Group 9: Communication Parameters

There is a built-in RS-485 serial interface, marked RJ-45 near to the control terminals. The pins are defined below:

8

1

RS-485

 

 

Serial interface

3: GND

 

 

1: Reserved 2: EV

 

 

4: SG-

5: SG+

6: Reserved

 

 

7: Reserved 8: Reserved

 

Each VFD-EL AC motor drive has a pre-assigned communication address specified by Pr.09.00. The RS485 master then controls each AC motor drive according to its communication address.

09.00

Communication Address

 

 

 

 

 

 

Settings

1 to 254

Factory Setting: 1

 

 

 

 

If the AC motor drive is controlled by RS-485 serial communication, the communication address for this drive must be set via this parameter. And the communication address for each AC motor drive must be different and unique.

09.01Transmission Speed

Factory Setting: 1

Settings

0

Baud rate 4800 bps (bits / second)

 

1

Baud rate 9600 bps

 

2

Baud rate 19200 bps

 

3

Baud rate 38400 bps

 

 

 

This parameter is used to set the transmission speed between the RS485 master (PC, etc.) and AC motor drive.

09.02Transmission Fault Treatment

Factory Setting: 3

Settings

0

Warn and keep operating

 

1

Warn and RAMP to stop

 

2

Warn and COAST to stop

 

3

No warning and keep operating

 

 

 

This parameter is set to how to react if transmission errors occur.

See list of error messages below (see section 3.6.)

4-84

Revision August 2008, 2ELE, V1.02

Page 127
Image 127
Delta Electronics VFD-EL manual RS-485, Group 9 Communication Parameters, 09.00