Delta Electronics VFD-EL manual Description of Parameter Settings, 00.02, Parameter Reset

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 69
Image 69
4.3 Description of Parameter Settings

Chapter 4 Parameters00.02

4.3 Description of Parameter Settings

Group 0: User Parameters

This parameter can be set during operation.

00.00Identity Code of the AC Motor Drive

Settings Read Only

Factory setting: ##

00.01Rated Current Display of the AC Motor Drive

Settings Read Only

Factory setting: #.#

Pr. 00.00 displays the identity code of the AC motor drive. The capacity, rated current, rated

voltage and the max. carrier frequency relate to the identity code. Users can use the following

table to check how the rated current, rated voltage and max. carrier frequency of the AC motor

drive correspond to the identity code.

Pr.00.01 displays the rated current of the AC motor drive. By reading this parameter the user

can check if the AC motor drive is correct.

 

 

115V/230V Series

 

kW

0.2

0.4

0.75

 

1.5

HP

0.25

0.5

1.0

 

2.0

Pr.00-00

0

2

4

 

6

Rated Output

1.6

2.5

4.2

 

7.5

Current (A)

 

 

 

 

 

 

Max. Carrier

 

 

12kHz

 

Frequency

 

 

 

 

 

 

 

 

2.2

3.0

8

11.0

3.7

5.0

10

17.0

 

 

460V Series

 

kW

0.4

0.75

 

1.5

HP

0.5

1.0

 

2.0

Pr.00-00

3

5

 

7

Rated Output

1.5

2.5

 

4.2

Current (A)

 

 

 

 

 

Max. Carrier

 

 

 

12kHz

Frequency

 

 

 

 

 

 

 

2.2

3.0

9

5.5

3.7

5.0

11

8.2

00.02

Parameter Reset

Factory Setting: 0

Settings 0 Parameter can be read/written

1All parameters are read-only

8Keypad lock

9All parameters are reset to factory settings (50Hz, 230V/400V or 220V/380V depends on Pr.00.12)

10All parameters are reset to factory settings (60Hz, 115V/220V/440V)

4-26

Revision August 2008, 2ELE, V1.02

Page 69
Image 69
Delta Electronics VFD-EL manual Description of Parameter Settings, 00.02, Parameter Reset