Chapter 4 Parameters

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

 

 

 

08.17

Auto Energy Saving

0: Disable

0

 

1: Enable

 

 

 

 

 

 

 

 

 

 

 

 

0: AVR function enable

 

 

08.18

AVR Function

1: AVR function disable

0

 

2: AVR function disable for decel.

 

 

 

 

 

 

 

3: AVR function disable for stop

 

 

 

 

 

 

 

08.19

Reserved

 

 

 

 

 

 

 

 

 

Compensation

0.0~5.0

0.0

 

08.20

Coefficient for Motor

 

 

 

Instability

 

 

 

 

 

 

 

 

Group 9 Communication Parameters

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

 

 

 

Setting

 

09.00

Communication

1 to 254

1

 

Address

 

 

 

 

 

 

 

 

 

 

 

 

0: Baud rate 4800bps

 

 

09.01

Transmission Speed

1: Baud rate 9600bps

1

 

2: Baud rate 19200bps

 

 

 

 

 

 

 

3: Baud rate 38400bps

 

 

 

 

 

 

 

 

 

0: Warn and keep operating

 

 

09.02

Transmission Fault

1: Warn and ramp to stop

3

 

 

 

Treatment

2: Warn and coast to stop

 

 

 

 

 

 

 

 

 

 

3: No warning and keep operating

 

 

 

 

 

 

 

09.03

Time-out Detection

0.1 ~ 120.0 seconds

0.0

 

0.0: Disable

 

 

 

 

 

 

 

 

 

 

09.04

Communication

0: 7,N,2 (Modbus, ASCII)

0

 

 

Protocol

1: 7,E,1 (Modbus, ASCII)

 

 

 

 

 

 

 

 

2: 7,O,1 (Modbus, ASCII)

 

 

 

 

3: 8,N,2 (Modbus, RTU)

 

 

 

 

 

 

 

Revision August 2008, 2ELE, V1.02

4-17

Page 60
Image 60