Chapter 4 Parameters

 

 

 

 

 

 

 

0=external terminal

 

 

Weights

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=internal terminal

 

 

Bit

1

1

0

1

0

0

 

 

MI1

 

 

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

 

 

MI6

04.28

Internal Terminal Status

 

 

 

 

 

 

Unit: 1

 

Settings

0 to 4095

 

 

 

 

 

 

Factory Setting: 0

This parameter is used to set the internal terminal action via keypad or communication.

For standard AC motor drive, the multi-function input terminals are MI1 to MI6 as shown in the following.

Weights Bit

0=set internal terminal to be OFF 1=set internal terminal to be ON

54 3 2 1 0 Manual backgroundMI1

Manual backgroundMI2 MI3 MI4 MI5 MI6

For example, if setting MI3, MI5 and MI6 to be ON, Pr.04.28 should be set to

bit5X25+bit4X24+bit2X22= 1X25+1X24+1X22= 32+16+4=52 as shown in the following.

Weights

 

 

 

 

 

 

0=OFF

 

 

 

 

 

 

1=ON

Bit

1

1

0

1

0

0

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

4-64

Revision August 2008, 2ELE, V1.02