Chapter 4 Parameters

Parameter

Explanation

Settings

Factory

Customer

Setting

01.04

Mid-Point Voltage

115V/230V series: 0.1V to 255.0V

10.0

 

 

 

 

(Vmid)

460V series: 0.1V to 510.0V

20.0

 

 

 

 

 

 

 

 

 

 

 

01.05

Minimum Output

0.10 to 600.0 Hz

1.50

 

Frequency (Fmin)

 

 

 

 

 

 

 

 

 

 

01.06

Minimum Output

115V/230V series: 0.1V to 255.0V

10.0

 

 

 

 

Voltage (Vmin)

460V series: 0.1V to 510.0V

20.0

 

 

 

 

 

 

 

 

 

 

 

01.07

Output Frequency

0.1 to 120.0%

110.0

 

Upper Limit

 

 

 

 

 

 

 

 

 

 

 

01.08

Output Frequency

0.0 to100.0 %

0.0

 

Lower Limit

 

 

 

 

 

 

 

 

 

 

 

01.09

Accel Time 1

0.1 to 600.0 / 0.01 to 600.0 sec

10.0

 

 

 

 

 

 

01.10

Decel Time 1

0.1 to 600.0 / 0.01 to 600.0 sec

10.0

 

 

 

 

 

 

01.11

Accel Time 2

0.1 to 600.0 / 0.01 to 600.0 sec

10.0

 

 

 

 

 

 

01.12

Decel Time 2

0.1 to 600.0 / 0.01 to 600.0 sec

10.0

 

 

 

 

 

 

01.13

Jog Acceleration

0.1 to 600.0 / 0.01 to 600.0 sec

1.0

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

01.14

Jog Deceleration

0.1 to 600.0 / 0.01 to 600.0 sec

1.0

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

01.15

Jog Frequency

0.10 Hz to Fmax (Pr.01.00) Hz

6.00

 

 

 

 

 

 

 

 

0: Linear Accel/Decel

 

 

 

Auto acceleration /

1: Auto Accel, Linear Decel

 

 

 

 

 

 

01.16

deceleration (refer

2: Linear Accel, Auto Decel

0

 

to Accel/Decel time

 

 

 

3: Auto Accel/Decel (Set by load)

 

 

 

setting)

 

 

 

 

4: Auto Accel/Decel (set by Accel/Decel

 

 

 

 

Time setting)

 

 

 

 

 

 

 

01.17

Acceleration S-

0.0 to 10.0 / 0.00 to 10.00 sec

0.0

 

Curve

 

 

 

 

 

 

 

 

 

 

01.18

Deceleration S-

0.0 to 10.0 / 0.00 to 10.00 sec

0.0

 

Curve

 

 

 

 

 

 

 

 

 

 

01.19

Accel/Decel Time

0: Unit: 0.1 sec

0

 

Unit

1: Unit: 0.01 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

4-4

Revision August 2008, 2ELE, V1.02

Page 47
Image 47