Chapter 4 Parameters
Group 2: Operation Method Parameters
02.00Source of First Master Frequency Command
Factory Setting: 1
02.09Source of Second Master Frequency Command
Factory Setting: 0
Settings 0 Digital keypad UP/DOWN keys or
10 to +10V from AVI
24 to 20mA from ACI
3
4Digital keypad potentiometer
These parameters set the Master Frequency Command Source of the AC motor drive.
The factory setting for master frequency command is 1. (digital keypad is optional.)
Setting 2: use the ACI/AVI switch on the AC motor drive to select ACI or AVI.
When the AC motor drive is controlled by external terminal, please refer to Pr.02.05 for details.
The first /second frequency/operation command is enabled/disabled by Multi Function Input
Terminals. Please refer to Pr.04.05 ~ 04.08.
02.01Source of First Operation Command
|
| Factory Setting: 1 |
Settings | 0 | Digital keypad (Digital keypad is optional) |
| 1 | External terminals. Keypad STOP/RESET enabled. |
| 2 | External terminals. Keypad STOP/RESET disabled. |
| 3 | |
|
| enabled. |
| 4 | |
|
| disabled. |
The factory setting for source of first operation command is 1. (digital keypad is optional.)
When the AC motor drive is controlled by external terminal, please refer to Pr.02.05/Pr.04.04
for details.
Revision August 2008, 2ELE, V1.02 |