Delta Electronics VFD-EL manual Group 2 Operation Method Parameters

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 80
Image 80
Manual background

Chapter 4 ParametersManual background

Group 2: Operation Method Parameters

02.00Source of First Master Frequency Command

Factory Setting: 1

02.09Source of Second Master Frequency Command

Factory Setting: 0

Settings 0 Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN. Last used frequency saved. (Digital keypad is optional)

10 to +10V from AVI

24 to 20mA from ACI

3RS-485 (RJ-45) communication

4Digital keypad potentiometer

These parameters set the Master Frequency Command Source of the AC motor drive.

The factory setting for master frequency command is 1. (digital keypad is optional.)

Setting 2: use the ACI/AVI switch on the AC motor drive to select ACI or AVI.

When the AC motor drive is controlled by external terminal, please refer to Pr.02.05 for details.

The first /second frequency/operation command is enabled/disabled by Multi Function Input

Terminals. Please refer to Pr.04.05 ~ 04.08.

02.01Source of First Operation Command

 

 

Factory Setting: 1

Settings

0

Digital keypad (Digital keypad is optional)

 

1

External terminals. Keypad STOP/RESET enabled.

 

2

External terminals. Keypad STOP/RESET disabled.

 

3

RS-485 (RJ-45)/USB communication. Keypad STOP/RESET

 

 

enabled.

 

4

RS-485 (RJ-45)/USB communication. Keypad STOP/RESET

 

 

disabled.

The factory setting for source of first operation command is 1. (digital keypad is optional.)

When the AC motor drive is controlled by external terminal, please refer to Pr.02.05/Pr.04.04

for details.

Revision August 2008, 2ELE, V1.02

4-37