Delta Electronics VFD-EL manual 08.08, 08.09, 08.10, 08.11, 08.12, 08.13, 08.14

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 123
Image 123
08.08

Chapter 4 Parameters08.09

When momentary power loss is detected, the AC motor drive will block its output and then wait for a specified period of time (determined by Pr.08.07, called Base-Block Time) before resuming operation. This parameter should be set at a value to ensure that any residual regeneration voltage from the motor on the output has disappeared before the drive is activated again.

This parameter also determines the waiting time before resuming operation after External Baseblock and Auto Restart after Fault (Pr.08.15).

08.08

Current Limit for Speed Search

Unit: 1

 

 

 

 

 

Settings

30 to 200%

Factory Setting: 150

Following a momentary power loss, the AC motor drive will start its speed search operation only if the output current is greater than the value set by Pr.08.08. When the output current is less than the value of Pr.08.08, the AC motor drive output frequency is at “speed synchronization point”. The drive will start to accelerate or decelerate back to the operating frequency at which it was running prior to the power loss.

 

 

 

 

 

 

Maximum Allowable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

Power Loss Time

 

 

 

 

 

 

 

 

08.05

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed Search

 

 

 

 

Synchronization

 

 

 

 

 

 

 

 

 

 

 

Detection

 

08.04=1

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

Baseblock Time

 

 

 

 

 

 

 

Frequency

 

08.06

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

08.05Allowable Power

08.04=2 Baseblock Time

08.06

08.09

Skip Frequency 1 Upper Limit

Unit: 0.01

08.10

Skip Frequency 1 Lower Limit

Unit: 0.01

08.11

Skip Frequency 2 Upper Limit

Unit: 0.01

08.12

Skip Frequency 2 Lower Limit

Unit: 0.01

 

 

 

08.13

Skip Frequency 3 Upper Limit

Unit: 0.01

08.14

Skip Frequency 3 Lower Limit

Unit: 0.01

 

Settings

0.00 to 600.0Hz

Factory Setting: 0.00

4-80

Revision August 2008, 2ELE, V1.02

Page 123
Image 123
Delta Electronics VFD-EL manual 08.08, 08.09, 08.10, 08.11, 08.12, 08.13, 08.14