Chapter 6 Fault Code Information and Maintenance

Fault

Fault Descriptions

 

Corrective Actions

Name

 

 

1.

Short-circuit at motor output: Check for

 

 

 

 

 

possible poor insulation at the output lines.

 

 

2.

Torque boost too high: Decrease the torque

 

Over-current during

 

compensation setting in Pr.07.02.

 

3.

Acceleration Time too short: Increase the

 

acceleration

 

 

Acceleration Time.

 

 

 

 

 

4.

AC motor drive output power is too small:

 

 

 

Replace the AC motor drive with the next

 

 

 

higher power model.

 

 

1.

Short-circuit at motor output: Check for

 

 

 

possible poor insulation at the output line.

 

Over-current during

2.

Deceleration Time too short: Increase the

 

 

Deceleration Time.

 

deceleration

 

 

3.

AC motor drive output power is too small:

 

 

 

 

 

Replace the AC motor drive with the next

 

 

 

higher power model.

 

 

1.

Short-circuit at motor output: Check for

 

 

 

possible poor insulation at the output line.

 

Over-current during

2.

Sudden increase in motor loading: Check for

 

 

possible motor stall.

 

constant speed operation

 

 

3.

AC motor drive output power is too small:

 

 

 

 

 

Replace the AC motor drive with the next

 

 

 

higher power model.

 

 

1.

When multi-function input terminals (MI3-MI9)

 

External Fault

 

are set to external fault, the AC motor drive

 

 

stops output U, V and W.

 

 

2.

Give RESET command after fault has been

 

 

 

cleared.

 

Internal EEPROM can not be

Return to the factory.

 

programmed.

 

 

 

 

Internal EEPROM can not be

Return to the factory.

 

programmed.

 

1.

Press RESET key to set all parameters to

 

Internal EEPROM can not be

 

 

factory setting.

 

read.

 

 

2.

Return to the factory.

 

 

 

Internal EEPROM can not be

1.

Press RESET key to set all parameters to

 

 

factory setting.

 

read.

 

 

2.

Return to the factory.

 

 

 

U-phase error

 

 

 

V-phase error

 

 

 

W-phase error

Return to the factory.

 

 

 

OV or LV

 

 

 

Temperature sensor error

 

 

Revision August 2008, 2ELE, V1.02

6-3

Page 164
Image 164
Delta Electronics VFD-EL Fault Descriptions Corrective Actions Name, Over-current during, Acceleration, Deceleration, Read