Delta Electronics VFD-EL manual 10.21, 10.22, 10.23

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 149
Image 149
10.21

Chapter 4 Parameters10.22

+

Setpoint

- 10.23

Input Freq.

Gain

10.10

P

10.02

I

10.03

D

10.04

 

 

+

 

 

Output

 

Integral

 

 

 

gain

+

 

 

 

Freq .

 

limit

 

 

 

 

Limit

 

 

 

 

 

10.05

+

10.07

 

 

 

 

 

 

 

PID feedback

10.01

Digital filter

10.06

Freq . Manual background Command

10.20Treatment of the Erroneous PID Feedback Level

Factory Setting: 0

Settings

0

Keep operating

 

1

Coast to stop

 

2

Ramp to stop

 

3

Ramp to stop and restart after time set in Pr.10.21

In PID control mode, it will act according to Pr.10.20 when erroneous PID feedback level occurs.

10.21

Restart Delay Time after Erroneous PID Deviation Level

Unit: 1

 

 

 

 

 

Settings

1 to 9999 sec

Factory Setting: 60

 

 

 

 

 

 

10.22

Set Point Deviation Level

Unit: 1

 

 

 

 

 

Settings

0 to 100%

Factory Setting: 0

 

 

 

 

 

 

10.23

Detection Time of Set Point Deviation Level

Unit: 1

 

 

 

 

 

Settings

1 to 9999 sec

Factory Setting: 10

 

 

 

 

When the deviation is less than Pr.10.22 (in the range of PID set point to Pr.10.22 X PID set point) for a time exceeding the setting of Pr.10.23, the AC motor drive will decelerate to stop to be constant pressure status (This deceleration time is the setting of Pr.01.12). The system will be ready when the deviation is within the range of PID set point to Pr.10.22 X PID set point during deceleration.

4-106

Revision August 2008, 2ELE, V1.02

Page 149
Image 149
Delta Electronics VFD-EL manual 10.21, 10.22, 10.23