Chapter 4 Parameters

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

Initial Frequency

0: by Current Freq Command

 

 

02.14

 

0

 

Selection (for

1: by Zero Freq Command

 

 

keypad & RS485)

2: by Frequency Display at Stop

 

 

 

 

 

 

 

 

 

 

 

02.15

Initial Frequency

0.00 ~ 600.0Hz

60.00

 

Setpoint (for keypad

 

 

& RS485)

 

 

 

 

 

 

 

 

 

Display the Master

Read Only

 

 

02.16

Bit0=1: by First Freq Source (Pr.02.00)

##

 

Freq Command

 

Bit1=1: by Second Freq Source (Pr.02.09)

 

 

Source

 

 

 

Bit2=1: by Multi-input function

 

 

 

 

 

 

 

 

 

 

 

 

 

Read Only

 

 

 

Display the

Bit0=1: by Digital Keypad

 

 

 

 

 

 

02.17

Operation

Bit1=1: by RS485 communication

##

 

 

Command Source

Bit2=1: by External Terminal 2/3 wire mode

 

 

 

 

 

 

 

 

Bit3=1: by Multi-input function

 

 

 

 

 

 

 

02.18

User-defined Value

0 to Pr.00.13

0

 

2 Setting

 

 

 

 

 

 

 

 

 

 

02.19

User-defined Value

0 to 9999

##

 

2

 

 

 

 

 

 

 

 

 

 

Group 3 Output Function Parameters

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

Setting

03.00

Multi-function

0: No function

8

 

 

Output Relay (RA1,

1: AC drive operational

 

 

 

RB1, RC1)

 

 

 

 

2: Master frequency attained

 

 

 

 

3: Zero speed

 

 

 

 

4: Over torque detection

 

 

 

 

5: Base-Block (B.B.) indication

 

 

 

 

6: Low-voltage indication

 

 

 

 

7: Operation mode indication

 

 

 

 

8: Fault indication

 

 

 

 

9: Desired frequency attained

 

 

 

 

10: Terminal count value attained

 

 

 

 

 

 

 

Revision August 2008, 2ELE, V1.02

4-7

Page 50
Image 50
Delta Electronics VFD-EL manual Parameter Explanation Settings Factory Customer