Chapter 4 Parameters

Group 4: Input Function Parameters

 

 

 

 

04.00

Keypad Potentiometer Bias

Unit: 0. 1

 

Settings

0.0 to 100.0%

Factory Setting: 0.0

04.01Keypad Potentiometer Bias Polarity

 

 

 

 

Factory Setting: 0

 

Settings

0

Positive Bias

 

 

 

1

Negative Bias

 

 

 

 

04.02

Keypad Potentiometer Gain

Unit: 0.1

 

 

 

 

 

Settings

0.1 to 200.0%

Factory Setting: 100.0

04.03Keypad Potentiometer Negative Bias, Reverse Motion Enable/Disable

Factory Setting: 0

Settings

0

No Negative Bias Command

 

1

Negative Bias: REV Motion Enabled

 

 

 

Example 1: Standard application

This is the most used setting. The user only needs to set Pr.02.00 to 04. The frequency command comes from keypad potentiometer.

60Hz

30Hz

0Hz

0V 5V 10V

Example 2: Use of bias

Pr.01.00=60Hz--Max. output Freq. Potentiometer

Pr.04.00 =0%--Bias adjustment Pr.04.01 =0--Positive bias Pr.04.02 =100%--Input gain

Pr.04.03 =0--No negative bias command

This example shows the influence of changing the bias. When the input is 0V the output frequency is 10 Hz. At mid-point a potentiometer will give 40 Hz. Once the Maximum Output Frequency is reached, any further increase of the potentiometer or signal will not increase the output frequency. (To use the full potentiometer range, please refer to Example 3.) The value of external input voltage/current 0- 8.33V corresponds to the setting frequency 10-60Hz.