Chapter 4 Parameters

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

4: 8,E,1 (Modbus, RTU)

 

 

 

 

5: 8,O,1 (Modbus, RTU)

 

 

 

 

6: 8,N,1 (Modbus, RTU)

 

 

 

 

7: 8,E,2 (Modbus, RTU)

 

 

 

 

8: 8,O,2 (Modbus, RTU)

 

 

 

 

9: 7,N,1 (Modbus, ASCII)

 

 

 

 

10: 7,E,2 (Modbus, ASCII)

 

 

 

 

11: 7,O,2 (Modbus, ASCII)

 

 

 

 

 

 

 

09.05

Reserved

 

 

 

 

 

 

 

 

09.06

Reserved

 

 

 

 

 

 

 

 

09.07

Response Delay

0 ~ 200 (unit: 2ms)

1

 

Time

 

 

 

 

 

 

 

 

 

 

 

Group 10 PID Control Parameters

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

0: Disable PID operation

 

 

 

 

1: Keypad (based on Pr.02.00)

 

 

10.00

PID Set Point

2: 0 to +10V from AVI

0

 

Selection

 

 

 

 

 

 

 

3: 4 to 20mA from ACI

 

 

 

 

4: PID set point (Pr.10.11)

 

 

 

 

 

 

 

 

 

0: Positive PID feedback from external

 

 

 

 

terminal AVI (0 ~ +10VDC)

 

 

 

 

1: Negative PID feedback from external

 

 

10.01

Input Terminal for

terminal AVI (0 ~ +10VDC)

0

 

PID Feedback

2: Positive PID feedback from external

 

 

 

 

 

 

terminal ACI (4 ~ 20mA)

 

 

 

 

3: Negative PID feedback from external

 

 

 

 

terminal ACI (4 ~ 20mA)

 

 

 

 

 

 

 

10.02

Proportional Gain

0.0 to 10.0

1.0

 

(P)

 

 

 

 

 

 

 

 

 

 

10.03

Integral Time (I)

0.00 to 100.0 sec (0.00=disable)

1.00

 

 

 

 

 

 

4-18

Revision August 2008, 2ELE, V1.02

Page 61
Image 61
Delta Electronics VFD-EL manual Parameter Explanation Settings Factory Customer