Delta Electronics VFD-EL manual Display Value, Function, 02.18

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 88
Image 88
Display Value

Chapter 4 ParametersFunction

These parameters are used to determinate the frequency at stop:

When setting Pr.02.14 to 0: the initial frequency will be current frequency.

When setting Pr.02.14 to 1: the initial frequency will be 0.

When setting Pr.02.14 to 2: the initial frequency will be Pr.02.15.

02.16Display the Master Freq Command Source

Settings Read Only

Factory setting: ##

You can read the master frequency command source by this parameter.

Display Value

1

2

4

Bit

Bit0=1

Bit1=1

Bit2=1

Function

Master Freq Command Source by First Freq Source (Pr.02.00).

Master Freq Command Source by Second Freq Source (Pr.02.09).

Master Freq Command Source by Multi-input function

02.17Display the Operation Command Source

Settings Read Only

Factory setting: ##

You can read the operation source by this parameter.

Display Value

1

2

4

8

Bit

Bit0=1

Bit1=1

Bit2=1

Bit3=1

Function

Operation Command Source by Digital Keypad

Operation Command Source by RS485 communication

Operation Command Source by External Terminal

Operation Command Source by Multi-input function

02.18

User-defined Value 2 Setting

Unit: 1

 

 

 

 

 

Settings

0 to Pr.00.13

Factory Setting: 0

 

 

 

 

Revision August 2008, 2ELE, V1.02

4-45

Page 88
Image 88
Delta Electronics VFD-EL manual Display Value, Function, 02.18