Chapter 4 Parameters

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

3: Enable. Operation status will change if

 

 

 

 

operation command source Pr.02.01 is

 

 

 

 

changed.

 

 

 

 

 

 

 

 

 

0: Decelerate to 0 Hz

 

 

02.06

Loss of ACI Signal

1: Coast to stop and display “AErr”

1

 

(4-20mA)

 

 

 

2: Continue operation by last frequency

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

0: by UP/DOWN Key

 

 

02.07

Up/Down Mode

1: Based on accel/decel time

0

 

2: Constant speed (Pr.02.08)

 

 

 

 

 

 

 

3: Pulse input unit (Pr.02.08)

 

 

 

 

 

 

 

 

Accel/Decel Rate of

 

 

 

 

Change of

 

 

 

02.08

UP/DOWN

0.01~10.00 Hz

0.01

 

 

Operation with

 

 

 

 

Constant Speed

 

 

 

 

 

 

 

 

 

 

0: Digital keypad UP/DOWN keys or Multi-

 

 

 

 

function Inputs UP/DOWN. Last used

 

 

 

Source of Second

frequency saved.

 

 

02.09

1: 0 to +10V from AVI

0

 

Frequency

 

 

 

 

Command

2: 4 to 20mA from ACI

 

 

 

 

3: RS-485 (RJ-45) communication

 

 

 

 

4: Digital keypad potentiometer

 

 

 

 

 

 

 

 

Combination of the

0: First Master Frequency Command

 

 

 

1: First Master Frequency Command+

 

 

 

First and Second

0

 

02.10

Second Master Frequency Command

 

Master Frequency

 

 

2: First Master Frequency Command -

 

 

 

Command

 

 

 

 

Second Master Frequency Command

 

 

02.11

Keypad Frequency

0.00 to 600.0Hz

60.00

 

Command

 

 

 

 

 

 

 

 

 

 

 

 

Communication

0.00 to 600.0Hz

60.00

 

02.12

Frequency

 

 

 

Command

 

 

 

 

 

 

 

 

 

The Selections for

0: Save Keypad & Communication

 

 

 

Frequency

 

 

 

Saving Keypad or

1: Save Keypad Frequency only

 

 

02.13

Communication

0

 

 

Frequency

 

 

 

 

Command

2: Save Communication Frequency only

 

 

 

 

 

 

 

 

 

 

 

4-6

Revision August 2008, 2ELE, V1.02

Page 49
Image 49
Delta Electronics VFD-EL manual Up/Down