Chapter 4 Parameters
| ||||
Prevention during | ||||
Operation, output | ||||
Detection | frequency decrease | |||
Level |
|
| Output Current | |
06.02 |
|
| ||
|
|
|
|
|
|
|
|
|
|
Output
Frequency
over-current stall prevention during operation
06.03
|
| Factory Setting: 0 |
Settings | 0 | |
| 1 | |
|
| After |
| 2 | |
|
| After |
| 3 | |
|
| torque is detected, keep running until OL1 or OL occurs. |
| 4 | |
|
| torque is detected, stop running. |
This parameter determines the operation mode of the drive after the
detected via the following method: if the output current exceeds the
(Pr.06.04) longer than the setting of Pr.06.05
message “OL2” is displayed. If a
detection (Pr.03.00=04), the output is on. Please refer to Pr.03.00 for details.
06.04 | Unit: 1 | ||
| Settings | 10 to 200% | Factory Setting: 150 |
|
|
|
|
This setting is proportional to the Rated Output Current of the drive.
06.05 | Unit: 0.1 | ||
| Settings | 0.1 to 60.0 sec | Factory Setting: 0.1 |
|
|
|
|
Revision August 2008, 2ELE, V1.02 |