Appendix C How to Select the Right AC Motor Drivek ⋅  3 ⋅VM ⋅ IM ⋅10−3 ≤ the _ capacity_ of _ AC _ motor _ drive(kVA)

2.3When it is running continuously

„The requirement of load capacity should be less than the capacity of AC motor drive(kVA)

The requirement of load capacity=

k P

η⋅ cosϕ the _ capacity _ of _ AC _ motor _ drive(kVA)

„The motor capacity should be less than the capacity of AC motor driveM

k k ⋅ IM ≤ the _ rated _ current _ of _ AC _ motor _ drive( A) 3 ⋅VM IM ⋅10−3 the _ capacity_ of _ AC _ motor _ drive(kVA)

„The current should be less than the rated current of AC motor drive(A)

k IM the _ rated _ current _ of _ AC _ motor _ drive( A)

Symbol explanation

PM

η

cosϕ

VM

IM

k

PC1

kS

nT nS

GD2

TL

tA

N

:Motor shaft output for load (kW)

:Motor efficiency (normally, approx. 0.85)

:Motor power factor (normally, approx. 0.75)

:Motor rated voltage(V)

:Motor rated current(A), for commercial power

:Correction factor calculated from current distortion factor (1.05-1.1, depending on PWM method)

:Continuous motor capacity (kVA)

:Starting current/rated current of motor

:Number of motors in parallel

:Number of simultaneously started motors

:Total inertia (GD2) calculated back to motor shaft (kg m2)

:Load torque

:Motor acceleration time

:Motor speed