Chapter 6 Fault Code Information and MaintenanceManual background

 

Fault

Fault Descriptions

 

Corrective Actions

 

 

Name

 

 

 

 

 

 

 

 

 

 

When (one of) the output terminal(s) is grounded,

 

 

 

short circuit current is more than 50% of AC motor

 

 

 

drive rated current, the AC motor drive power

 

 

 

module may be damaged.

 

 

Ground fault

NOTE: The short circuit protection is provided

 

 

for AC motor drive protection, not for

 

 

 

protection of the user.

 

 

 

1.

Check whether the IGBT power module is

 

 

 

 

damaged.

 

 

 

2.

Check for possible poor insulation at the

 

 

 

 

output line.

 

 

 

1.

Check if the motor is suitable for operation by

 

 

Auto accel/decel failure

 

AC motor drive.

 

 

2.

Check if the regenerative energy is too large.

 

 

 

 

 

 

3.

Load may have changed suddenly.

 

 

 

1.

Check the RS485 connection between the AC

 

 

 

 

motor drive and RS485 master for loose wires

 

 

 

 

and wiring to correct pins.

 

 

Communication Error

2.

Check if the communication protocol, address,

 

 

 

transmission speed, etc. are properly set.

 

 

 

 

 

 

 

3.

Use the correct checksum calculation.

 

 

 

4.

Please refer to group 9 in the chapter 5 for

 

 

 

 

detail information.

 

 

Software protection failure

Return to the factory.

 

 

 

 

 

 

Analog signal error

Check the wiring of ACI

 

 

 

 

 

 

 

 

1.

Check parameter settings (Pr.10.01) and

 

 

 

 

AVI/ACI wiring.

 

 

PID feedback signal error

2.

Check for possible fault between system

 

 

 

 

response time and the PID feedback signal

 

 

 

 

detection time (Pr.10.08)

 

 

Phase Loss

Check input phase wiring for loose contacts.

 

 

 

 

 

 

6-4

Revision August 2008, 2ELE, V1.02

Page 165