Delta Electronics VFD-EL manual Appendix A Specifications, General Specifications, Enviromental

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 174
Image 174
Enviromental

 

 

Appendix A Specifications

 

 

General Specifications

 

 

AVR, accel/decel S-Curve, over-voltage/over-current stall prevention, 5 fault

 

 

records, reverse inhibition, momentary power loss restart, DC brake, auto

 

 

torque/slip compensation, auto tuning, adjustable carrier frequency, output

 

Operation Functions

frequency limits, parameter lock/reset, PID control, external counter,

 

 

MODBUS communication, abnormal reset, abnormal re-start, power-saving,

 

 

fan control, sleep/wake frequency, 1st/2nd frequency source selections,

 

 

1st/2nd frequency source combination, NPN/PNP selection

 

Protection Functions

Over voltage, over current, under voltage, external fault, overload, ground

 

fault, overheating, electronic thermal, IGBT short circuit, PTC

 

 

 

 

6-key, 7-segment LED with 4-digit, 4 status LEDs, master frequency, output

 

Display Keypad (optional)

frequency, output current, custom units, parameter values for setup and lock,

 

 

faults, RUN, STOP, RESET, FWD/REV

 

Built-in EMI Filter

For 230V 1-phase and 460V 3-phase models.

 

 

 

 

Enclosure Rating

IP20

Conditions

 

 

Pollution Degree

2

Installation Location

-10oC to 50oC (40oC for side-by-side mounting) Non-Condensing and not

 

Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust

Enviromental

Ambient Temperature

Below 90% RH (non-condensing)

Ambient Humidity

 

 

frozen

 

Storage/ Transportation

-20 oC to 60 oC

 

Temperature

 

 

 

 

 

Vibration

9.80665m/s2 (1G) less than 20Hz, 5.88m/s2 (0.6G) at 20 to 50Hz

Approvals

 

 

 

 

Revision August 2008, 2ELE, V1.02

A-3