Chapter 4 Parameters

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

 

 

 

08.02

DC Brake Time

0.0 to 60.0 sec

0.0

 

during Stopping

 

 

 

 

 

 

 

 

 

 

08.03

Start-Point for DC

0.00 to 600.0Hz

0.00

 

Brake

 

 

 

 

 

 

 

 

 

 

 

 

0: Operation stops after momentary power

 

 

 

 

loss

 

 

 

Momentary Power

1: Operation continues after momentary

 

 

 

power loss, speed search starts with the

0

 

08.04

Loss Operation

 

Master Frequency reference value

 

 

Selection

 

 

 

 

 

 

 

 

2: Operation continues after momentary

 

 

 

 

power loss, speed search starts with the

 

 

 

 

minimum frequency

 

 

08.05

Maximum Allowable

0.1 to 5.0 sec

2.0

 

Power Loss Time

 

 

 

 

 

 

 

 

 

 

 

 

0: Disable speed search

 

 

08.06

Base-block Speed

1: Speed search starts with last frequency

1

 

Search

command

 

 

 

 

 

 

2: Starts with minimum output frequency

 

 

 

 

 

 

 

08.07

B.B. Time for Speed

0.1 to 5.0 sec

0.5

 

 

Search

 

 

 

08.08

Current Limit for

30 to 200%

150

 

Speed Search

 

 

 

 

 

 

 

 

 

 

08.09

Skip Frequency 1

0.00 to 600.0 Hz

0.00

 

Upper Limit

 

 

 

 

 

 

 

 

 

 

08.10

Skip Frequency 1

0.00 to 600.0 Hz

0.00

 

Lower Limit

 

 

 

 

 

 

 

 

 

 

08.11

Skip Frequency 2

0.00 to 600.0 Hz

0.00

 

Upper Limit

 

 

 

 

 

 

 

 

 

 

08.12

Skip Frequency 2

0.00 to 600.0 Hz

0.00

 

Lower Limit

 

 

 

 

 

 

 

 

 

 

08.13

Skip Frequency 3

0.00 to 600.0 Hz

0.00

 

Upper Limit

 

 

 

 

 

 

 

 

 

 

08.14

Skip Frequency 3

0.00 to 600.0 Hz

0.00

 

Lower Limit

 

 

 

 

 

 

 

 

 

 

08.15

Auto Restart After

0 to 10 (0=disable)

0

 

 

Fault

 

 

 

 

 

 

 

 

08.16

Auto Reset Time at

0.1 to 6000 sec

60.0

 

Restart after Fault

 

 

 

 

 

 

 

 

 

 

 

4-16

Revision August 2008, 2ELE, V1.02

Page 59
Image 59