Delta Electronics VFD-EL Summary of Parameter Settings, Group 0 User Parameters, Explanation

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 45
Image 45

Chapter 4 Parameters4.1 Summary of Parameter Settings

4.1 Summary of Parameter Settings

: The parameter can be set during operation.

Group 0 User Parameters

Parameter

Explanation

Settings

Factory

Customer

Setting

00.00

Identity Code of the

Read-only

##

 

 

AC motor drive

 

 

 

 

 

 

 

 

00.01

Rated Current

Read-only

#.#

 

 

Display of the AC

 

 

 

 

motor drive

 

 

 

 

 

 

 

 

 

 

0: Parameter can be read/written

 

 

 

 

1: All parameters are read only

 

 

 

 

8: Keypad lock

 

 

00.02

Parameter Reset

9: All parameters are reset to factory settings

0

 

 

 

(50Hz, 230V/400V or 220V/380V depends on

 

 

 

 

Pr.00.12)

 

 

 

 

10: All parameters are reset to factory

 

 

 

 

settings (60Hz, 220V/440V)

 

 

 

 

 

 

 

 

 

0: Display the frequency command value

 

 

 

 

(Fxxx)

 

 

 

 

1: Display the actual output frequency (Hxxx)

 

 

00.03

Start-up Display

2: Display the content of user-defined unit

0

 

Selection

 

 

(Uxxx)

 

 

 

 

 

 

 

 

3: Multifunction display, see Pr.00.04

 

 

 

 

4: FWD/REV command

 

 

 

 

 

 

 

 

 

0: Display the content of user-defined unit

 

 

 

 

(Uxxx)

 

 

 

 

1: Display the counter value (c)

 

 

 

 

2: Display the status of multi-function input

 

 

 

Content of Multi-

terminals (d)

 

 

00.04

 

0

 

function Display

3: Display DC-BUS voltage (u)

 

 

 

 

 

 

4: Display output voltage (E)

 

 

 

 

5: Display PID analog feedback signal value

 

 

 

 

(b) (%)

 

 

 

 

6: Output power factor angle (n)

 

 

 

 

 

 

 

4-2

Revision August 2008, 2ELE, V1.02

Page 45
Image 45
Delta Electronics VFD-EL manual Summary of Parameter Settings, Group 0 User Parameters, Explanation, Factory, Customer