Chapter 5 Troubleshooting

5.9 Motor cannot Run

Check No

Motor cannot run keypad for normal display

 

 

 

Yes

Reset after clearing

Yes Check if there is any

fault and then RUN

 

fault code displayed

 

 

No

Check if non-fuse breaker and magnetic contactor are ON

 

Yes

 

Check if input

No

voltage is normal

 

 

Yes

 

 

 

 

 

 

No Set them to ON

Check if any faults occur, such as Lv, PHL or disconnection

It can run when

Input "RUN"

No

no faults occur

 

 

command

 

 

 

 

by keypad

 

 

 

 

 

 

 

 

 

 

 

Maybe AC motor drive has malfunction or misoperation due to noise. Please contact DELTA.

Press RUN key to check if it can run

Press UP key to set frequency

Yes

Press UP to check if motor can run

No

Yes

No Check if input FWD or REV command

Yes

No Set frequency or not

No

No

Check if the wiring

Yes

of terminal MI1

 

 

and between

 

 

MI2-DCM is correct

 

 

No

Correct connection

Change switch or relay

Modify frequency

Yes

setting

 

if upper bound freq. and setting freq. is lower than the min. output freq.

No

No

Check if the parameter setting and wiring of analog signal and multi-step speed

are correct

Yes

Change defective

potentiometer and

 

 

relay

 

 

Motor has malfunction

 

 

 

Check if there is any

No

 

 

 

 

 

 

Maybe AC motor drive has malfunction.

 

 

 

 

 

 

output voltage from

 

 

 

 

 

 

 

 

No

 

 

 

terminals U, V and W

 

 

Please contact DELTA.

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

If load is too large

 

Yes

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

Check if motor

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if the setting

 

 

 

 

 

 

connection

 

 

Connect correctly

 

 

Yes

is correct

 

 

 

 

 

 

of torque

 

 

 

 

 

 

 

 

compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is correct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor is locked due to large load, please reduce load.

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

For example, if there is a brake, check if it is released.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Increase the setting of

 

 

 

 

 

 

 

 

 

 

 

torque compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-6

Revision August 2008, 2ELE, V1.02

Page 157
Image 157
Delta Electronics VFD-EL manual Motor cannot Run