| Chapter 4 Parameters |
| |
Parameter | Explanation | Settings | Factory | Customer |
Setting | ||||
|
| 2: Enabled during constant speed operation. |
|
|
|
| After the |
|
|
|
| running. |
|
|
|
| 3: Enabled during accel. After the |
|
|
|
| is detected, keep running until OL1 or OL |
|
|
|
| occurs. |
|
|
|
| 4: Enabled during accel. After the |
|
|
|
| is detected, stop running. |
|
|
|
|
|
|
|
06.04 | 10 to 200% | 150 |
| |
Detection Level |
| |||
|
|
|
| |
|
|
|
|
|
06.05 | 0.1 to 60.0 sec | 0.1 |
| |
Detection Time |
| |||
|
|
|
| |
|
|
|
|
|
| Electronic Thermal | 0: Standard motor (self cooled by fan) |
|
|
06.06 | Overload Relay | 1: Special motor (forced external cooling) | 2 |
|
Selection |
| |||
|
| 2: Disabled |
|
|
|
|
|
|
|
06.07 | Electronic Thermal | 30 to 600 sec | 60 |
|
Characteristic |
| |||
|
|
|
| |
|
|
|
|
|
|
| 0: No fault | 0 |
|
|
| 1: Over current (oc) |
|
|
06.08 | Present Fault | 2: Over voltage (ov) |
|
|
Record |
|
| ||
|
|
|
| |
|
| 3: IGBT Overheat (oH1) |
|
|
|
| 4: Reserved |
|
|
|
| 5: Overload (oL) |
|
|
|
| 6: Overload1 (oL1) |
|
|
|
| 7: Motor over load (oL2) |
|
|
|
|
|
|
|
06.09 | Second Most | 8: External fault (EF) |
|
|
| Recent Fault Record | 9: Current exceeds 2 times rated current |
|
|
|
|
|
| |
|
| during accel.(ocA) |
|
|
|
| 10: Current exceeds 2 times rated current |
|
|
|
| during decel.(ocd) |
|
|
|
| 11: Current exceeds 2 times rated current |
|
|
|
| during steady state operation (ocn) |
|
|
|
| 12: Ground fault (GFF) |
|
|
|
| 13: Reserved |
|
|
|
|
|
|
|