Chapter 4 Parameters

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

2: Enabled during constant speed operation.

 

 

 

 

After the over-torque is detected, stop

 

 

 

 

running.

 

 

 

 

3: Enabled during accel. After the over-torque

 

 

 

 

is detected, keep running until OL1 or OL

 

 

 

 

occurs.

 

 

 

 

4: Enabled during accel. After the over-torque

 

 

 

 

is detected, stop running.

 

 

 

 

 

 

 

06.04

Over-Torque

10 to 200%

150

 

Detection Level

 

 

 

 

 

 

 

 

 

 

06.05

Over-Torque

0.1 to 60.0 sec

0.1

 

Detection Time

 

 

 

 

 

 

 

 

 

 

 

Electronic Thermal

0: Standard motor (self cooled by fan)

 

 

06.06

Overload Relay

1: Special motor (forced external cooling)

2

 

Selection

 

 

 

2: Disabled

 

 

 

 

 

 

 

06.07

Electronic Thermal

30 to 600 sec

60

 

Characteristic

 

 

 

 

 

 

 

 

 

 

 

 

0: No fault

0

 

 

 

1: Over current (oc)

 

 

06.08

Present Fault

2: Over voltage (ov)

 

 

Record

 

 

 

 

 

 

 

 

3: IGBT Overheat (oH1)

 

 

 

 

4: Reserved

 

 

 

 

5: Overload (oL)

 

 

 

 

6: Overload1 (oL1)

 

 

 

 

7: Motor over load (oL2)

 

 

 

 

 

 

 

06.09

Second Most

8: External fault (EF)

 

 

 

Recent Fault Record

9: Current exceeds 2 times rated current

 

 

 

 

 

 

 

 

during accel.(ocA)

 

 

 

 

10: Current exceeds 2 times rated current

 

 

 

 

during decel.(ocd)

 

 

 

 

11: Current exceeds 2 times rated current

 

 

 

 

during steady state operation (ocn)

 

 

 

 

12: Ground fault (GFF)

 

 

 

 

13: Reserved

 

 

 

 

 

 

 