Chapter 4 Parameters
This parameter allows the user to reset all parameters to the factory settings except the fault records (Pr.06.08 ~ Pr.06.12).
50Hz: Pr.01.00 and Pr.01.01 are set to 50Hz and Pr.01.02 will be set by Pr.00.12.
60Hz: Pr.01.00 and Pr.01.01 are set to 60Hz and Pr.01.02 is set to 115V, 230V or 460V. When Pr.00.02=1, all parameters are
00.03
| Factory Setting: 0 |
Settings 0 | Display the frequency command value (Fxxx) |
1 | Display the actual output frequency (Hxxx) |
2 | Display the output current in A supplied to the motor |
| (Axxx) |
3 | Display the content of |
4 | FWD/REV command |
This parameter determines the
00.04Content of
| Factory Setting: 0 | ||||
|
|
|
| ||
Settings 0 | Display the content of |
|
|
| |
1 | Display the counter value which counts the number of |
|
|
| |
| |||||
pulses on TRG terminal |
|
|
| ||
|
|
|
| ||
|
|
|
| ||
2 | Display status of |
|
|
| |
3 | Display the actual DC BUS voltage in VDC of the AC |
|
|
| |
| |||||
motor drive |
|
|
| ||
4 | Display the output voltage in VAC of terminals U/T1, |
|
|
| |
| |||||
V/T2, W/T3 to the motor. |
|
|
| ||
|
|
|
| ||
5 | Display PID analog feedback signal value in % |
|
|
| |
6 | Display the power factor angle in º of terminals U/T1, |
|
|
| |
| |||||
V/T2, W/T3 to the motor |
|
|
| ||
7 | Display the output power in kW of terminals U, V and W |
|
|
| |
| |||||
to the motor. |
|
|
| ||
|
| ||||
8 | Display PID setting and feedback signal. |
|
| ||
|
|
|
|
|
|