Delta Electronics VFD-EL 00.10, Reserved, 00.11, 00.12, 50Hz Base Voltage Selection, 00.13, 00.14

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 73
Image 73
00.10

Chapter 4 ParametersReserved

00.10

Reserved

00.11

Reserved

00.12

50Hz Base Voltage Selection

Factory Setting: 0

 

Settings

0

230V/400V

 

 

 

 

1

220V/380V

 

 

This parameter determines the base voltage for 50Hz.

 

 

 

 

 

 

00.13

User-defined Value 1 (correspond to max. frequency)

Unit: 1

 

 

Settings

 

0 to 9999

Factory Setting: 0

This parameter corresponds to max. frequency.

When Pr.00-13 is not set to 0, “F” will disappear in frequency mode and the right-most digit will blink. Many ranges will be changed to Pr.00.13, including potentiometer, UP/DOWN key, AVI, ACI, multi-step, JOG function and PID function.

When Pr.00.13 is not set to 0 and the frequency source is from communication, please use Pr.02-18 to change frequency setting because it can’t be set at address 2001H.

 

00.14

Position of Decimal Point of User-defined Value 1

Unit: 1

 

 

Settings

0 to 3

Factory Setting: 0

 

 

 

 

 

It is used to set the position of decimal point of Pr.00.13.

Example: when you want to set 10.0, you need to set Pr.00.13 to 100 and Pr.00.14 to 1.

4-30

Revision August 2008, 2ELE, V1.02

Page 73
Image 73
Delta Electronics VFD-EL manual 00.10, Reserved, 00.11, 00.12, 50Hz Base Voltage Selection, 00.13, 00.14