Chapter 4 Parameters

 

Parameter

Explanation

Settings

 

Factory

Customer

 

Setting

10.04

Derivative Control

0.00 to 1.00 sec

 

0.00

 

(D)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.05

Upper Bound for

0 to 100%

 

100

 

Integral Control

 

 

 

 

 

 

 

 

 

 

 

 

 

10.06

Primary Delay Filter

0.0 to 2.5 sec

 

0.0

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

10.07

PID Output Freq

0 to 110%

 

100

 

Limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PID Feedback

 

 

 

 

10.08

Signal Detection

0.0 to 3600 sec (0.0 disable)

 

60.0

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

Treatment of the

0: Warn and RAMP to stop

 

 

 

 

 

 

 

 

10.09

Erroneous PID

1: Warn and COAST to stop

 

0

 

 

Feedback Signals

2: Warn and keep operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.10

Gain Over the PID

0.0 to 10.0

 

1.0

 

Detection Value

 

 

 

 

 

 

 

 

 

 

 

 

 

10.11

Source of PID Set

0.00 to 600.0Hz

 

0.00

 

point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.12

PID Feedback Level

1.0 to 50.0%

 

10.0

 

 

 

 

 

 

 

10.13

Detection Time of

0.1 to 300.0 sec

 

5.0

 

PID Feedback

 

 

 

 

 

 

 

 

 

 

 

 

 

10.14

Sleep/Wake Up

0.0 to 6550 sec

 

0.0

 

Detection Time

 

 

 

 

 

 

 

 

 

 

 

 

 

10.15

Sleep Frequency

0.00 to 600.0 Hz

 

0.00

 

 

 

 

 

 

 

10.16

Wakeup Frequency

0.00 to 600.0 Hz

 

0.00

 

 

 

 

 

 

 

10.17

Minimum PID

0: By PID control

 

0

 

Output Frequency

1: By minimum output frequency (Pr.01.05)

 

 

Selection

 

 

 

 

 

 

 

 

 

PID Control

 

 

 

 

10.18

Detection Signal

1.0 to 99.9

 

99.9

 

 

Reference

 

 

 

 

 

 

 

 

 

 

10.19

PID Calculation

0: Series mode

 

0

 

Mode Selection

1: Parallel mode

 

 

 

 

 

 

 

 

 

 

 

 

Revision August 2008, 2ELE, V1.02

4-19

Page 62
Image 62