Delta Electronics VFD-EL manual Weights, 0=Active, 1=Off, 04.27

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 106
Image 106
Weights

Chapter 4 Parameters0=Active

For Example:

If Pr.04.26 displays 52, it means MI1, MI2 and MI4 are active.

The display value 52= 32+16+4 =1 X 25+ 1X 24 + 1X 22 = bit 6 X 25+ bit 5 X 24 + bit 3 X 22

Weights

 

 

 

 

 

 

0=Active

Bit

1

1

0

1

0

0

1=Off

 

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

04.27

Internal/External Multi-function Input Terminals Selection

Unit: 1

 

Settings

0 to 4095

Factory Setting: 0

 

This parameter is used to select the terminals to be internal terminal or external terminal. You

 

can activate internal terminals by Pr.04.28. A terminal cannot be both internal terminal and

 

external terminal at the same time.

 

 

For standard AC motor drive, the multi-function input terminals are MI1 to MI6 as shown in the

 

following.

 

 

Weights

 

 

 

 

 

 

0=external terminal

Bit

5

4

3

2

1

0

1=internal terminal

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

The Setting method is convert binary number to decimal number for input.

For example: if setting MI3, MI5, MI6 to be internal terminals and MI1, MI2, MI4 to be external terminals. The setting value should be bit5X25+bit4X24+bit2X22= 1X25+1X24+1X22= 32+16+4=52 as shown in the following.

Revision August 2008, 2ELE, V1.02

4-63

Page 106
Image 106
Delta Electronics VFD-EL manual Weights, 0=Active, 1=Off, 04.27