When Pr.02.07 is set to 2: increase/decrease the frequency by Pr.02.08.

Chapter 4 Parameters02.11

These parameters determine the increase/decrease of the master frequency when operated via the Multi-function Inputs when Pr.04.05~Pr.04.08 are set to 10 (Up command) or 11 (Down command).

When Pr.02.07 is set to 0: increase/decrease the frequency by using UP/DOWN key. It is valid only when the AC motor drive is running.

When Pr.02.07 is set to 1: increase/decrease the frequency by acceleration/deceleration settings. It is valid only when the AC motor drive is running.

When Pr.02.07 is set to 2: increase/decrease the frequency by Pr.02.08.

When Pr.02.07 is set to 3: increase/decrease the frequency by Pr.02.08 (unit: pulse input).

02.11

Keypad Frequency Command

Unit: 0.01

 

 

 

 

 

Settings

0.00 to 600.0Hz

Factory Setting: 60.00

 

This parameter can be used to set frequency command or read keypad frequency command.

 

 

 

02.12

Communication Frequency Command

Unit: 0.01

 

 

 

 

 

Settings

0.00 to 600.0Hz

Factory Setting: 60.00

This parameter can be used to set frequency command or read communication frequency command.

02.13The Selections for Saving Keypad or Communication Frequency Command

Factory Setting: 0

Settings

0

Save Keypad & Communication Frequency

 

1

Save Keypad Frequency only

 

2

Save Communication Frequency only

 

 

 

This parameter is used to save keypad or RS-485 frequency command.

02.14Initial Frequency Selection (for keypad & RS485)

 

 

 

 

Factory Setting: 0

 

Settings

0

By Current Freq Command

 

 

 

1

By Zero Freq Command

 

 

 

2

By Frequency Display at Stop

 

 

 

 

02.15

Initial Frequency Setpoint (for keypad & RS485)

Unit: 0.01

 

Settings

0.00 ~ 600.0Hz

Factory Setting: 60.00

 

 

 

 

 