Delta Electronics VFD-EL manual Present Fault Record 06.09 Second Most Recent Fault Record

Models: VFD-EL

1 209
Download 209 pages 9.33 Kb
Page 114
Image 114
06.08Present Fault Record

Chapter 4 ParametersManual background

06.08Present Fault Record

06.09Second Most Recent Fault Record

06.10Third Most Recent Fault Record

06.11Fourth Most Recent Fault Record

06.12Fifth Most Recent Fault Record

Factory Setting: 0

Readings

0

No fault

 

1

Over-current (oc)

 

2

Over-voltage (ov)

 

3

IGBT Overheat (oH1)

 

4

Reserved

 

5

Overload(oL)

 

6

Overload (oL1)

 

7

Motor Overload (oL2)

 

8

External Fault (EF)

 

9

Hardware protection failure (HPF)

 

10

Current exceeds 2 times rated current during accel.(ocA)

 

11

Current exceeds 2 times rated current during decel.(ocd)

 

12

Current exceeds 2 times rated current during steady state

 

 

operation (ocn)

 

13

Reserved

 

14

Phase-loss (PHL)

 

15

Reserved

 

16

Auto accel/decel failure (CFA)

 

17

Software/password protection (codE)

 

18

Power Board CPU WRITE Failure (cF1.0)

 

19

Power Board CPU READ Failure (cF2.0)

 

20

CC, OC Hardware protection failure (HPF1)

 

21

OV Hardware protection failure (HPF2)

 

22

GFF Hardware protection failure (HPF3)

 

23

OC Hardware protection failure (HPF4)

 

24

U-phase error (cF3.0)

 

25

V-phase error (cF3.1)

 

26

W-phase error (cF3.2)

 

27

DCBUS error (cF3.3)

 

28

IGBT Overheat (cF3.4)

 

 

 

Revision August 2008, 2ELE, V1.02