Chapter 4 Parameters

10.17Minimum PID Output Frequency Selection

 

 

 

 

 

Factory Setting: 0

 

Settings

0

By PID control

 

 

 

1

By Minimum output frequency (Pr.01.05)

 

 

 

 

 

This is the source selection of minimum output frequency when control is by PID.

 

 

 

 

 

10.18

PID Control Detection Signal Reference

Unit: 0.1

 

 

 

 

 

 

 

Settings

1.0 to 99.9

Factory Setting: 99.9

 

 

 

 

 

 

When Pr.00.04 is set to 8, it will display 00:00 as follows.

This parameter is used only for display and has no relation with Pr.00.13, Pr.00.14, Pr.02.18 and Pr.02.19.

Setpoint

Feedback value

(the max. value you would like to convert)

10.19PID Calculation Mode Selection

Factory Setting: 0

Settings

0

 

Series mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Parallel mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Series mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

P

 

 

 

I

 

 

Integral

+

 

 

 

Output

 

Digital

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

gain

+

 

 

 

 

Freq.

 

 

Freq.

 

 

 

 

 

 

 

 

 

 

 

 

 

filter

 

Setpoint

 

 

 

 

 

 

 

 

 

 

limit

 

 

 

 

 

Limit

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

10.02

10.03

 

 

10.05

+

 

10.07

10.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.04

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Freq.

 

 

 

PID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gain

 

 

 

 

 

 

 

feedback

 

 

 

 

 

 

 

10.10

 

 

 

 

 

 

 

 

10.01

 

 

 

 

 

 

 

 

 

 

Parallel mode

Revision August 2008, 2ELE, V1.02

4-105

Page 148
Image 148