Chapter 4 Parameters
10.17Minimum PID Output Frequency Selection
|
|
|
|
| Factory Setting: 0 |
| Settings | 0 | By PID control |
| |
|
| 1 | By Minimum output frequency (Pr.01.05) |
| |
|
|
|
| ||
This is the source selection of minimum output frequency when control is by PID. | |||||
|
|
|
|
| |
10.18 | PID Control Detection Signal Reference | Unit: 0.1 | |||
|
|
|
|
|
|
| Settings | 1.0 to 99.9 | Factory Setting: 99.9 | ||
|
|
|
|
|
|
When Pr.00.04 is set to 8, it will display 00:00 as follows.
This parameter is used only for display and has no relation with Pr.00.13, Pr.00.14, Pr.02.18 and Pr.02.19.
Setpoint | Feedback value |
(the max. value you would like to convert)
10.19PID Calculation Mode Selection
Factory Setting: 0
Settings | 0 |
| Series mode |
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
| 1 |
| Parallel mode |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Series mode |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
+ |
|
|
| P |
|
|
| I |
|
| Integral | + |
|
|
| Output |
| Digital |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
| gain | + |
|
|
|
| Freq. |
|
| Freq. | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| filter |
| |||||||||
Setpoint |
|
|
|
|
|
|
|
|
|
| limit |
|
|
|
|
| Limit |
|
| Command | |||
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
- |
|
|
| 10.02 | 10.03 |
|
| 10.05 | + |
| 10.07 | 10.06 |
|
| |||||||||
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
| D |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 10.04 |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Input Freq. |
|
|
| PID |
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Gain |
|
|
|
|
|
|
| feedback |
|
|
|
|
|
|
| ||||||||
10.10 |
|
|
|
|
|
|
|
| 10.01 |
|
|
|
|
|
|
|
|
|
| ||||
Parallel mode
Revision August 2008, 2ELE, V1.02 |