Chapter 4 Parameters
DC Brake during
DC Brake during stopping is used to shorten the stopping time and also to hold a stopped load in position. For high inertia loads, a brake resistor for dynamic brake may also be needed for fast decelerations.
08.04Momentary Power Loss Operation Selection
|
| Factory Setting: 0 |
Settings | 0 | Operation stops (coast to stop) after momentary power loss. |
| 1 | Operation continues after momentary power loss, speed search |
|
| starts with the Master Frequency reference value. |
| 2 | Operation continues after momentary power loss, speed search |
|
| starts with the minimum frequency. |
This parameter determines the operation mode when the AC motor drive restarts from a momentary power loss.
08.05 | Maximum Allowable Power Loss Time | Unit: 0.1 | |
| Settings | 0.1 to 5.0 sec | Factory Setting: 2.0 |
|
|
|
|
If the duration of a power loss is less than this parameter setting, the AC motor drive will resume operation. If it exceeds the Maximum Allowable Power Loss Time, the AC motor drive output is then turned off (coast stop).
The selected operation after power loss in Pr.08.04 is only executed when the maximum allowable power loss time is ≤5 seconds and the AC motor drive displays “Lu”.
But if the AC motor drive is powered off due to overload, even if the maximum allowable power loss time is ≤5 seconds, the operation mode as set in Pr.08.04 is not executed. In that case it starts up normally.
08.06Base Block Speed Search
Factory Setting: 1
Settings 0 Disable
1Speed search starts with last frequency command
2Speed search starts with minimum output frequency (Pr.01.05)
This parameter determines the AC motor drive restart method after External Base Block is enabled.
Revision August 2008, 2ELE, V1.02 |