Chapter 4 Parameters

03.08

Fan Control

 

 

 

 

 

Factory Setting: 0

 

Settings

0

Fan always ON

 

 

1

1 minute after AC motor drive stops, fan will be OFF

 

 

2

Fan ON when AC motor drive runs, fan OFF when AC motor drive

 

 

 

stops

 

 

3

Fan ON when preliminary heatsink temperature attained

 

 

 

 

This parameter determines the operation mode of the cooling fan.

03.09Reserved

03.10Reserved

03.11

Brake Release Frequency

Unit: 0.01

 

Settings

0.00 to 600.0Hz

Factory Setting: 0.00

 

 

 

03.12

Brake Engage Frequency

Unit: 0.01

 

Settings

0.00 to 600.0Hz

Factory Setting: 0.00

 

 

 

 

These two parameters are used to set control of mechanical brake via the output terminals (Relay) when Pr.03.00is set to 21. Refer to the following example for details.

Example:

1.Case 1: Pr.03.12 Pr.03.11

2.Case 2: Pr.03.12 Pr.03.11

Frequency

Output

Case 1: Pr.03.12

Pr. 03.11

Case 2: Pr.03.12

Time

Run/Stop

Case 1: Pr.03.00=21

Case 2: Pr.03.00=21

Revision August 2008, 2ELE, V1.02

4-51

Page 94
Image 94
Delta Electronics VFD-EL manual 03.08, 03.11, 03.12