Chapter 4 Parameters

This parameter sets the Mid-Point Voltage of any V/f curve. With this setting, the V/f ratio between Minimum Frequency and Mid-Point Frequency can be determined. This parameter must be equal to or greater than Minimum Output Voltage (Pr.01.06) and equal to or less than Maximum Output Voltage (Pr.01.02).

01.05

Minimum Output Frequency (Fmin)

Unit: 0.01

 

 

Settings

0.10 to 600.0Hz

 

Factory Setting: 1.50

 

 

 

 

This parameter sets the Minimum Output Frequency of the AC motor drive. This parameter

 

must be equal to or less than Mid-Point Frequency (Pr.01.03).

 

 

 

 

 

 

01.06

Minimum Output Voltage (Vmin)

Unit: 0.1

 

 

Settings

115V/230V series

0.1 to 255.0V

Factory Setting: 10.0

 

 

 

460V series

0.1 to 510.0V

Factory Setting: 20.0

 

 

 

 

 

 

 

This parameter sets the Minimum Output Voltage of the AC motor drive. This parameter must be equal to or less than Mid-Point Voltage (Pr.01.04).

The settings of Pr.01.01 to Pr.01.06 have to meet the condition of Pr.01.02 Pr.01.04 Pr.01.06 and Pr.01.01 Pr.01.03 Pr.01.05.

01.07

Output Frequency Upper Limit

Unit: 0.1

 

Settings 0.1 to 120.0%

Factory Setting: 110.0

 

 

 

This parameter must be equal to or greater than the Output Frequency Lower Limit (Pr.01.08). The Maximum Output Frequency (Pr.01.00) is regarded as 100%.

Output Frequency Upper Limit value = (Pr.01.00 * Pr.01.07)/100.

01.0801.07

Voltage

Output Frequency

Output Frequency

Lower Limit

Upper Limit

01.02

 

 

 

 

Maximum

 

 

 

 

Output

 

 

 

 

Voltage

 

 

 

 

01.04

 

 

 

 

Mid-point

 

 

 

 

Voltage

 

The limit of

 

 

 

 

 

 

Output

 

 

 

 

Frequency

 

01.06

 

 

Frequency

Minimum

01.05

01.03

01.01

01.00

Output

Minimum

Mid-point

Maximum Voltage

Maximum

Voltage

Output

Freq.

Frequency

Output

 

 

Freq.

 

(Base Frequency)

Frequency

V/f Curve

4-32

Revision August 2008, 2ELE, V1.02

Page 75
Image 75
Delta Electronics VFD-EL manual 01.05, 01.06, 01.07