TOC

TOC

F-45

TROUBLESHOOTING & REPAIR

F-45

 

 

ROTOR VOLTAGE TEST (continued)

 

Return to Section

Return to Section TOC

Return to Section TOC

Return to Master

Return to Master TOC

Return to Master TOC

10. If the meter reading indicates battery

voltage, about 12 to 14 VDC, the rotor

may be open, or the brushes may be faulty

or not making proper contact with the slip

rings. Perform the Rotor Resistance Test,

and

Brush and Slip Ring Service

Proc dure.

 

11. If the voltage measures about 3 to 5

VDC, the generator is not building-up to

normal output even though the flashing cir-

cuit appears to be functioning normally.

This condition could be caused by one of

several failed components or connections.

Continue with the following test.

12. Check the field bridge rectifier, (D3) and

capacitor (C3); also check the wiring and

terminals connecting them. See the wiring

diagram.

 

13. Perform the Rotor Resistance Test.

14. Perform the

Stator Short Circuit and

Ground Test.

 

15. When the Stator short circuit and ground test has been completed, reconnect leads #7 and #9 to the field bridge rectifier, (D3). All other stator leads should remain discon- nected and isolated at this time.

16. Be sure that there are no leads of any kind across any of the stator windings, except the #7 - #9 winding. Examine stator wiring for damage, pinched leads, chafed insula- tion, etc. If necessary, disconnect and iso- late the stator output leads as close to the starter as possible. See wiring diagram.

17. All of these disconnected leads should be insulated, and/or positioned so they cannot come in contact with any other wiring or chassis ground and cannot be damaged by moving parts when the engine is running.

18. Re-start the machine and measure the rotor voltage.

19. If rotor voltage continues to read signifi- cantly lower than 50 VDC, the Stator is probably defective and should be replaced.

Note: The field bridge rectifier and field capac- itor may appear to function normally when test- ed independently, but may malfunction when placed under the stress or normal operation. For this reason, It is recommended that the bridge rectifier and the capacitor be replaced with known good components before replacing the stator.

Return to Section TOC

Return to Master TOC

RANGER 305D

Page 99
Image 99
Lincoln Electric SVM175-A service manual Rotor Voltage Test