INSTALLATION
A-9 A-9
RANGER 305D
Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOC
Return to Master TOC Return to Master TOC Return to Master TOC Return to Master TOC
1. Install the double-pole, double-throw switch
betweenthe power company meter and the premis-
es disconnect. Switch rating must be the same or
greater than the customerʼs premises disconnect
and service over-current protection.
2. Take necessary steps to assure load is limited to
the capacity of the Ranger 305D by installing a 50
amp, 240 VACdouble-pole circuit breaker.
Maximum continuous rated load for each leg of the
240 VAC auxiliary is 40 amperes. Loading above
the rated output will reduce output voltage below
the allowable +/- 10% of rated voltage, which may
damage appliances or other motor-driven equip-
ment and may result in overheating of the Ranger
305D engine and/or alternator windings.
3. Install a 50 amp, 120/240 VAC plug (NEMA Type
14-50 to the double-pole circuit breaker using No.
6, 4-conductor cable of the desired length. (The50
amp, 120/240 VACplug is available in the optional
K802R plug kit or as part number T12153-9.
4. Plug this cable into th 50 amp, 120/240 VACrecep-
tacle on the Ranger 305D case front.