A-9

INSTALLATION

A-9

1. Install the double-pole, double-throw switch

3. Install a 50 amp, 120/240 VAC plug (NEMA Type

between the power company meter and the premis-

14-50 to the double-pole circuit breaker using No.

es disconnect. Switch rating must be the same or

6, 4-conductor cable of the desired length. (The 50

greater than the customerʼs premises disconnect

amp, 120/240 VAC plug is available in the optional

and service over-current protection.

K802R plug kit or as part number T12153-9.

 

2. Take necessary steps to assure load is limited to

4. Plug this cable into th 50 amp, 120/240 VAC recep-

the capacity of the Ranger 305D by installing a 50

tacle on the Ranger 305D case front.

 

amp, 240 VAC double-pole circuit breaker.

 

 

Maximum continuous rated load for each leg of the

 

 

 

240 VAC auxiliary is 40 amperes. Loading above

 

 

 

the rated output will reduce output voltage below

 

 

 

the allowable +/- 10% of rated voltage, which may

 

 

 

damage appliances or other motor-driven equip-

 

 

 

ment and may result in overheating of the Ranger

 

 

 

305D engine and/or alternator windings.

 

 

RANGER 305D

Page 15
Image 15
Lincoln Electric SVM175-A service manual Installation