Stratum 3 clock

2. Set the options on the Stratum 3 (ST3) clock board (see Table 17).

Table 17. ST3 clock board option switch settings

Switch

Status/Results

 

 

SW1

OFF = minor alarm never output

Minor alarm

ON = minor alarm is output if holdover occurs

control

 

 

 

SW2

OFF = major alarm is output and fail lamp lights if 5 VDC

Major Alarm

power is lost and 4 kHz output is lost

Control

ON = major alarm is output and fail lamp lights if 5 VDC

 

 

power is lost and 4 kHz output is lost and holdover occurs

 

 

NOTE:

Only SW 1 and SW2 are used. SW1 controls the output of alarm signals from the Stratum 3 clock board.

3.Set the options on the composite clock timing output board (TOCA) per Table 18.

4.Set the Stratum 2/Stratum 3 switch to the STRATUM 3 position.

Table 18. Composite clock timing output board (TOCA)

Switch

 

Range in feet (meters)

 

 

 

 

 

 

 

 

 

 

 

 

 

500

1000

1.0

500

1000

1500

2000

2500

3000

 

 

(0.3)

(152)

(305)

(457)

(710)

(772)

(914)

 

 

 

 

 

 

 

 

 

OFF

OFF

 

 

 

 

 

 

 

ON

OFF

 

 

 

 

 

 

 

OFF

ON

 

 

 

 

 

 

 

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

Set switches 1 and 2 according to the distance from the Stratum 3 clock to the DEFINITY system. Set switch 3 to ON. Set switch 4 to OFF.